Part Number Hot Search : 
M5206 BD672 00BZX C16FGE MBR10 MA60771A 2SD2066 STBK568
Product Description
Full Text Search
 

To Download W68-XXXXX Datasheet File

  If you can't view the Datasheet, Please click here to try to view without PDF Reader .  
 
 


  Datasheet File OCR Text:
 W6/W9 series
Magnetic Hydraulic Circuit Breakers
Features
* Designed for the international market. UL Recognized, CSA Certified, and VDE approved. * Ratings to 50 amps. * Heavy duty #10-32 stud connections. (W9) * Optional 10 amp auxiliary switch. * Optional snap-in mounting. (W6) www..com * Several delay curve options. * Trip-free operation.
Typical Resistance and Impedance
Current (Amps) 0.2 1.0 2.0 5.0 10.0 20.0 30.0 40.0 50.0 DC Resistance (Ohms) 90 1.2 0.28 0.04 0.013 0.004 0.0027 0.002 0.0015 50/60 Hz. Impedance (Ohms) 90 1.2 0.28 0.04 0.013 0.005 0.004 0.002 0.0015 400 Hz. Impedance (Ohms) 180 2.0 0.50 0.05 0.025 0.0065 0.004 0.003 0.0025
Tolerance: 0.1 - 4.99 15%; 5 - 9.99 20%; 10 - 15 25%; 16 - 30 50%.
Agency Approvals
Recognized as Supplementary Protector under UL 1077 File . E69543. CSA: Certified as a Supplementary Protector. File LR15734. VDE: Approved to VDE 0642/EN 60 934 (Circuit Breakers for Equipment) License No. 73782. UL:
Mechanical/Environmental Data
Operating Temperature: -40C to +85C. Humidity: Meets requirements of Mil-STD-202 method 103. Shock: Tested per Mil-STD-202, method 213, test condition C (100g @ 6 ms). Vibration:Tested per Mil-STD-202, method 201, 10-55 Hz., 0.06" (1.52mm) total excursion in 2 planes. Fungus And Moisture Resistance: Special moisture resistant finish applied to all ferrous parts. Plastic parts are made of inherently fungus resistant material. Marking: W6 units have ON and OFF molded on the rocker of rocker actuated units (rocker actuated VDE units have international "1" and "0"). W9 units have ON and OFF molded into the area at the base of the toggle. International "1" and "0" symbols are marked on the toggle for both W6 and W9. Mounting: Panel mounted units are mounted with two #6-32 screws from the front of the panel. Metric models for use with M3 x 0.5 screws are available. Units with snap-in mounting option snap through the front of the panel. To maintain published performance specifications, units should not be mounted more than 90 from their normal upright position. Weight: Approximately 2.5 ounces per pole.
Electrical Data
Auxiliary Switch: See Auxiliary Switch Ratings Table 2 for details. Calibration: Breakers will hold 100% of rated current. Breakers may trip between 101% and 124% of rated load (149% for 400 Hz. units and 134% for AC/DC units). Breakers must trip at 125% of rated load and above (150% for 400 Hz. units and 135% for AC/DC units). Dielectric Strength: 50/60 or 400 Hz., 1500V: DC, 1100V. Insulation Resistance: 100 Megohms at 500VDC. Endurance: 10,000 on/off cycles - 6000 at rated load, 4000 at no load. Units tested at six cycles per minute, 1 second on and 9 seconds off at 25C ambient.
Approvals and Ratings Table 1
W6 Series
Maximum Voltage 65 277 277 277/480 250 250 250
UL/CSA (All Circuit Functions)
Frequency (Hz) DC 50/60 50/60 50/60 400 400 400 Current Phase 1 1 3O-Wye 1 1 3O-Wye Interrupting Rating (Amps) 0.2 - 50 0.2 - 20 21 - 50 0.2 - 20 0.2 - 20 21 - 50 0.2 - 20 Capacity (Amps) 2,000 5,000 2,500 5,000 2,500 1,250 2,500
W6 Series
Maximum Voltage 65 250 250 415/240
VDE (Circuit Function X)
Frequency (Hz) DC 50/60 50/60 50/60 Current Phase 1 1 3O Interrupting Rating (Amps) 0.2-50 0.2-30 31-50 0.2-30 Capacity (Amps) 2,000 5,000 2,000 5,000
W9 Series
Maximum Voltage 65 277 277/480 250 250
UL/CSA (All Circuit Functions)
Frequency (Hz) DC 50/60 50/60 400 400 Current Phase 1 3O-Wye 1 3O-Wye Interrupting Rating (Amps) 0.2 - 50 0.2 - 50 0.2 - 20 0.2 - 50 0.2 - 50 Capacity (Amps) 2,000 5,000 5,000 2,500 2,500
W9 Series
Maximum Voltage 65 250 250 415/240
VDE (Circuit Function X)
Frequency (Hz) DC 50/60 50/60 50/60 Current Phase 1 1 3O Interrupting Rating (Amps) 0.2-50 0.2-30 31-50 0.2-30 Capacity (Amps) 2,000 5,000 2,000 5,000
Approvals and Ratings Table 2
UL/CSA
Switch Number A Voltage 50/60 Hz. 125 Current (Amps) 10 Terminals WxTxL .093 x .020 x .250 (2.36 x .51 x 6.40)
VDE
Switch Number V1 V2 V3 Voltage 50/60 Hz. 250 250 250 Current (Amps) 10 5 0.1 Terminals WxTxL .110 x .020 x .280 (2.79 x .51 x 7 .11)
Time vs. Current Trip Curves For W6 Series and W9 Series
AC 50/60 Hz.
DC & 50/60 Hz. 400 Hz.
10,000 1000
CURVE 0 NON-TIME DELAY
TRIP TIMES OVERLOAD @ 50/60 Hz. & DC @ 400 Hz. 125% 150% 200% 400% 600% 800% 100 ms max. 55 ms max. 30 ms max. 15 ms max. 12 ms max. 12 ms max. May Trip 100 ms max. 30 ms max. 15 ms max. 12 ms max. 12 ms max.
10,000 1000
CURVE 2 AC VOLTAGE 50/60 Hz.
OVERLOAD TRIP TIMES (SEC.) 125% 200% 400% 600% 800% 1000% 10 - 150 2.2 - 20 .2 - 2 .03 - .75 .007 - .15 .005 - .04
10,000 1000
CURVE 3 AC VOLTAGE 50/60 Hz.
OVERLOAD TRIPTIMES (SEC.) 125% 200% 400% 600% 800% 1000% 1 - 15 .15 - 1.5 .03 - .25 .007 - .15 .003 - .08 .003 - .04
TIME IN SECONDS
TIME IN SECONDS
100 10 1 .1 .01
100 10 1 .1 .01
TIME IN SECONDS
100 10 1 .1 .01
.001 0
100 200 300 400 500 600 700 800 900 1000 1 100 1200 125 150 LOAD CURRENT AS A PERCENT OF BREAKER RATING
.001 0
100 200 300 400 500 600 700 800 900 1000 1 100 1200 125 150 LOAD CURRENT AS A PERCENT OF BREAKER RATING
.001 0
100 200 300 400 500 600 700 800 900 1000 1 100 1200 125 150 LOAD CURRENT AS A PERCENT OF BREAKER RATING
10,000 1000
MOTOR START CURVE 10 HIGH INRUSH 50/60 Hz. AC
OVERLOAD TRIP TIMES (SEC.) 125% 40 - 500 200% 9 - 100 400% 2 - 20 600% .8 - 10 800% .1 - 4.5 1000% .009 - 2
10,000 1000
CURVE 12 HIGH INRUSH 50/60 Hz.
OVERLOAD TRIP TIMES (SEC.) 125% 200% 400% 600% 800% 1000% 10 - 150 3 - 25 .5 - 2.5 .15 - 1 .015 - .7 .009 - .35
10,000 1000
CURVE 13 HIGH INRUSH 50/60 Hz.
OVERLOAD TRIP TIMES (SEC.) 125% 200% 400% 600% 800% 1000% .8 - 30 .15 - 2.5 .03 - .3 .02 - .15 .009 - .12 .009 - .09
TIME IN SECONDS
TIME IN SECONDS
TIME IN SECONDS
www..com
100 10 1 .1 .01 .001 0
100 10 1 .1 .01
100 10 1 .1 .01
100 200 300 400 500 600 700 800 900 1000 1 100 1200 125 150 LOAD CURRENT AS A PERCENT OF BREAKER RATING
.001 0
100 200 300 400 500 600 700 800 900 1000 1 100 1200 125 150 LOAD CURRENT AS A PERCENT OF BREAKER RATING
.001 0
100 200 300 400 500 600 700 800 900 1000 1 100 1200 125 150 LOAD CURRENT AS A PERCENT OF BREAKER RATING
DC
10,000 1000
CURVE 2 DC VOLTAGE
OVERLOAD TRIP TIMES (SEC.) 125% 200% 400% 600% 800% 1000% 2 - 55 .60 - 8 .1 - 1.5 .02 - .5 .004 - .05 .004 - .025
10,000 1000
CURVE 3 DC VOLTAGE
OVERLOAD TRIP TIMES (SEC.) 125% 200% 400% 600% 800% 1000% .6 - 7 .16 - 1.5 .03 - .25 .01 - .13 .004 - .05 .003 - .015
10,000 1000
CURVE 53 DC HIGH INRUSH
OVERLOAD TRIP TIMES (SEC.) 125% 80 - 700 200% 15 - 150 400% 2 - 20 600% .70 - 10 800% .10 - 3 1000% .01 - .1
TIME IN SECONDS
TIME IN SECONDS
100 10 1 .1 .01
100 10 1 .1 .01
TIME IN SECONDS
100 10 1 .1 .01
.001 0
100 200 300 400 500 600 700 800 900 1000 1 100 1200 125 150 LOAD CURRENT AS A PERCENT OF BREAKER RATING
.001 0
100 200 300 400 500 600 700 800 900 1000 1 100 1200 125 150 LOAD CURRENT AS A PERCENT OF BREAKER RATING
.001 0
100 200 300 400 500 600 700 800 900 1000 1 100 1200 125 150 LOAD CURRENT AS A PERCENT OF BREAKER RATING
AC/DC
10,000 1000
AC 400 Hz.
CURVE 34 DC, 50/60 Hz. STANDARD DELAY
OVERLOAD TRIP TIMES (SEC.) 135% 200% 400% 600% 800% 1000% 1 - 90 .60 - 20 .095 - 2 .02 - .95 .002 - .45 .002 - .09
10,000 1000
CURVE 2 AC VOLTAGE 400 Hz.
OVERLOAD TRIP TIMES (SEC.) 150% 200% 400% 600% 800% 1000% 5 - 60 2.2 - 20 .3 - 3.2 .01 - .17 .006 - .06 .005 - .045
10,000 1000
CURVE 3 AC VOLTAGE 400 Hz.
OVERLOAD TRIP TIMES (SEC.) 150% 200% 400% 600% 800% 1000% .55 - 5.5 .18 - 2 .02 - .2 .006 - .075 .004 - .05 .004 - .035
TIME IN SECONDS
100 10 1 .1 .01
TIME IN SECONDS
100 10 1 .1 .01
TIME IN SECONDS
100 10 1 .1 .01
.001 0
100 200 300 400 500 600 700 800 900 1000 1 100 1200 125 150 LOAD CURRENT AS A PERCENT 135 OF BREAKER RATING
.001 0
100 200 300 400 500 600 700 800 900 1000 1 100 1200 125 150 LOAD CURRENT AS A PERCENT OF BREAKER RATING
.001 0
100 200 300 400 500 600 700 800 900 1000 1 100 1200 125 150 LOAD CURRENT AS A PERCENT OF BREAKER RATING
Note: For instantaneous curves for all voltages refer to Curve 0 Non-Time Delay under the AC 50/60 Hz. heading.
Pulse Tolerance Specifications
Pulse tolerance is defined as a single pulse of a half sine wave (1/2 cycle or 8 milliseconds) that will not trip the breaker. An inertia wheel for increased pulse tolerance is available by specifying "P" after the time delay curve number in the ordering information. The table at right lists pulse tolerance values of standard and inertia delay models.
Time Delay Curve 2 3 10 12 13 2 3 Pulse Tolerance Value Standard 7 .5 6 18 18 18 6.5 5.5 Inertia Delay 18 18 30 30 30 18 18
Voltage AC 50/60 Hz.
AC 400 Hz.
To determine pulse tolerance multiply breaker rating by value in table. For example, a 2A breaker with time delay curve 3 has a standard pulse tolerance of 12A (2A x 6). The same breaker with an inertia delay has a pulse tolerance of 36A (2A x 18).
Ordering Information
W6 Series
Typical Part No.
1. Circuit Breaker Mounting: W = #6-32 mounting threads. M = M3.0 x 0.5 mounting threads. X = Snap-in mounting. (Not available in rocker actuated models.) 2. Number of Poles: 67 = Single pole 68 = Two pole 69 = Three pole X = Series trip 9 = Red toggle
B
W 67- X
2
Q
1
2- 20
70 = Four pole
3. Circuit Function: (Only X is VDE approved) A = Series trip with auxiliary switch (.093" QC) 4. Actuator: (One actuator per pole) 1 = Black toggle 3 = Black rocker 2 = White toggle 4 = White rocker
5 = Red rocker 6 = Grey rocker
5. Termination: Q = .250" QC (DIN 46 244) 25A Max. VDE
Note: "T" termination must be used for all ratings of 31 amps or above.
S = #8-32 screw
T = #10-32 screw
6. Maximum Line Voltage: (See Table 1 for current ranges) UL/CSA 1 = 277VAC, 50/60 Hz. VDE TYPES 2 = 277/480 TYPES 3 = 250VAC, 400 Hz. 5 www..com= 65VDC 7 = AC/DC 277VAC or 65VDC (Delay curve 34 must be specified.) 7. Time Delay Curve: 0 = Instantaneous 2 = Standard delay 3 = Short delay 53 = DC high inrush 8. Amp Rating: 0.20 0.50 0.25 0.75 1.0 1.5 2.0 2.5
1 = 250VAC, 415/240VAC 5 = 65VDC 7 = AC/DC 250VAC, 415/240VAC, 65VDC (Delay curve 34 must be specified.)
10 = AC high inrush (Motor start) 12 = AC high inrush version of #2 13 = AC high inrush version of #3 34 = Combination AC/DC standard delay 3.0 3.5 4.0 5.0 6.0 7 .0 7 .5 8.0
Notes: Curves may be specified with increased pulse tolerance for 1/2 cycle by adding "P" after curve, See delay curve section for availability and details.
9.0 10.0
11.0 12.0
15.0 20.0
25.0 30.0
35.0 40.0
45.0 50.0
Consult factory for other values.
9. VDE Approval: (See Table 2 for auxiliary switch ratings) Blank = UL/CSA approved breaker V = VDE approved breaker without auxiliary switch V1 = VDE approved breaker with 10 amp VDE auxiliary switch W67-A2Q12-5 W67-A2Q12-10 W67-X2Q10-3 W67-X2Q10-5 W67-X2Q12-2 W67-X2Q12-3 W67-X2Q12-5 W67-X2Q12-7 W67-X2Q12-10 W67-X2Q12-15 W67-X2Q12-20 W67-X2Q12-30 W67-X2Q13-1 W67-X2Q13-2 W67-X2Q13-3 W67-X2Q13-10 W67-X2Q13-15 W67-X2Q13-20
V2 = VDE approved breaker with 5 amp VDE auxiliary switch V3 = VDE approved breaker with 0.1 amp VDE auxiliary switch
Stock Items - We recommend that our authorized distributors stock the following items for immediate delivery.
W67-X2Q13-25 W67-X2Q13-30 W67-X2Q50-5 W67-X2Q50-10 W67-X2Q52-5 W67-X2Q52-10 W67-X2Q52-15 W67-X2Q52-20 W67-X2Q52-30 W67-X2Q110-15 W67-X2Q110-20 W68-X2Q12-3 W68-X2Q12-5 W68-X2Q12-7 W68-X2Q12-10 W68-X2Q12-15 W68-X2Q12-20 W68-X2Q12-25 W68-X2Q12-30 W68-X2Q13-15 W68-X2Q110-10 W68-X2Q110-20 W69-X2Q12-5 W69-X2Q12-10 W69-X2Q12-15 W69-X2Q12-20 W69-X2Q12-25 W69-X2Q12-30 W69-X2Q110-20 W69-X2Q110-30
Ordering Information
W9 Series
1. Circuit Breaker Mounting: W = #6-32 mounting threads. 2. Number of Poles: 91 = Single pole
Typical Part No.
M = M3.0 x 0.5 mounting threads. 93 = Three pole X = Series trip 94 = Four pole
B
W
91- X
1
1
2-
20
92 = Two pole
3. Circuit Function: (Only X is VDE approved) A = Series trip with auxiliary switch (.093" QC) 4. Actuator: (One actuator per pole): 1 = Black toggle 2 = White toggle
5. Maximum Line Voltage: (See Table 1 for current ranges) UL/CSA 1 = 277VAC, 50/60 Hz. VDE 1 = 250VAC, 415/240VAC TYPES 2 = 277/480 TYPES 5 = 65VDC 3 = 250VAC, 400 Hz. 7 = AC/DC 250VAC, 415/240VAC, 65VDC 5 = 65VDC (Delay curve 34 must be specified.) 7 = AC/DC 277VAC or 65VDC (Delay curve 34 must be specified.) 6. Time Delay Curve: 0 = Instantaneous 2 = Standard delay 3 = Short delay 53 = DC high inrush 7. Amp Rating: 0.20 0.75 0.25 1.0 0.50 1.5 10 = AC high inrush (Motor start) 12 = AC high inrush version of #2 13 = AC high inrush version of #3 34 = Combination AC/DC standard delay 2.0 2.5 3.0 3.5 4.0 5.0 6.0 7 .0 7 .5 8.0 9.0 10.0
Notes: Curves may be specified with increased pulse tolerance for 1/2 cycle by adding "P" after curve. See delay curve section for availability and details.
11.0 12.0 15.0
20.0 25.0 30.0
35.0 40.0 45.0
50.0
Consult factory for other values
8. VDE Approval: (See Table 2 for auxiliary switch ratings) Blank = UL/CSA approved breaker V = VDE approved breaker without auxiliary switch V1 = VDE approved breaker with 10 amp VDE auxiliary switch
V2 = VDE approved breaker with 5 amp VDE auxiliary switch V3 = VDE approved breaker with 0.1 amp VDE auxiliary switch
Stock Items - We recommend that our authorized distributors stock the following items for immediate delivery.
W91-X112-1 W91-X112-2 W91-X112-3 W91-X112-5 W91-X112-7 W91-X112-10 W91-X112-15 W91-X112-20 W91-X112-40 W91-X112-50 W91-X113-5 W91-X113-10 W91-X113-15 W91-X150-5 W91-X152-10 W91-X152-15 W91-X152-20 W91-X152-30 W91-X152-40 W91-X152-50 W91-X1110-20 W92-X112-1 W92-X112-2 W92-X112-3 W92-X112-5 W92-X112-7 W92-X112-10 W92-X112-15 W92-X112-20 W92-X112-25 W92-X112-30 W92-X112-40 W92-X112-50 W92-X113-15 W92-X113-20 W92-X1110-20 W92-X1110-30 W93-X112-5 W93-X112-10 W93-X112-15 W93-X112-20 W93-X112-25 W93-X112-30 W93-X112-40 W93-X112-50 W93-X1110-20 W93-X1110-30
Outline Dimensions - Toggle Actuator Models.
W6 Series
Panel Mounting Cutout
.235 (5.97) LINE A 1.640 (41.66) .245 (6.22) O .625 +.010 -.000 15.88 +0.25 -0.00 1 PER POLE .750 (19.05)
O N
(
)
1.660 (42.16)
29
1.530 (38.86) OFF B L AD O
30
1.048 (26.62)
www..com
2.040 (51.82)
.67 (17 .02)
O .156 (3.96) [2 PLACES PER POLE]
W6 Series 1 Pole
O .590 (15.00) .750 (19.05) 1.500 (38.10) 2.250 (57 .15) 3.000 (76.20)
2 Pole
3 Pole
4 Pole
2.000 (50.80) 1.22 (31.00)
1.660 (42.16) 1.05 (26.67)
6.32 TH'D. .14 (3.56) DP TYP . . M3 X 0.5 OPTIONAL Note: Multi-pole models furnished with separate handle tie hardware.
VDE Models W/Screw Terminals
UL/CSA Models W/Screw Terminals
.235 (5.9) 2.032 (51.61)
UL/CSA/VDE Models W/Aux. Switch
2.38 "A" STYLE (60.45) LINE .827 (20.85) 1.058 (26.87) C NO NC
LINE LINE
.416 (10.57)
1.530 (38.86)
LOAD LOAD
LOAD
Notes: 1. Terminal protrusion dimensions are referenced from back of mounting panel. 2. Main terminals are male quick connect type .250 (6.35) wide x .031 (.79) thick x .377 (9.58) long. Optional 8-32 x .250 (6.35) or 10-32 x .250 (6.35) screw type. 3. Panel mounting cutout detail mtg. detail tol.: .005 (.13) unless noted. Add additional cutouts to correspond to number of poles. Outline drawing tolerance .015 (.38) unless noted. Dimensions in brackets ( ) are in millimeters.
Outline Dimensions - Rocker Actuator Models
W6 Series
1.640 (41.66) .390 (9.91) .180 (4.57) LOAD 1.530 (38.86) LINE A D 2.000 (50.80) .388 (9.86) 2.600 (66.04) .805 (20.45) .375 (9.53)
1 Pole
.750 (19.05)
2, 3 & 4 Pole
3.000 (76.20) 2.250 (57 .15) 1.500 (38.10) 2 POLE 3 POLE 4 POLE
1.30 (33.0) 1.660 (42.16)
ON OFF
ON OFF
ON OFF
ON OFF
ON OFF
.235 (5.97) 2.430 (61.72) TAPPED FOR #6-32 M3 X 0.5 OPTIONAL
.375 (9.53)
.750 (19.05)
.750 (19.05)
.750 (19.05)
Panel Mounting www..com Cutout
.750 (19.05) .375 (9.53) .750 (19.05) .750 (19.05) .205 (5.21)
VDE Rocker Marking
.750 (19.05) .375 (9.53)
1.250 (31.75) 1.660 (42.16)
2.000 (50.80)
I O
.388 (9.86) 2.600 (66.04)
Notes: 1. Outline drawing tolerance .015 (.38) unless noted. Dimensions in brackets ( ) are in millimeters. 2. Mounting Detail Tol.: .005 (.13) unless noted
1 POLE 2 POLE 3 POLE 4 POLE
.750 (19.05) 1.500 (38.10) 2.250 (57 .15) 3.000 (76.20)
O .156 (3.96) TYP 2 . PER POLE
TAPPED FOR #6-32 M3 X 0.5 OPTIONAL
Outline Dimensions - Snap-in Mounted Models
W6 Series
1.640 (41.66) .245 (6.22)
1 Pole
.750 (19.05)
2 Pole
1.500 (38.10)
3 Pole
2.250 (57 .15)
.235 (5.97)
.128 (3.25) O N
ON 29
1.110 (28.19)
ON
ON
ON
ON
ON
1.530 (38.86) OFF
30
2.650 (67 .31)
OFF
OFF
OFF
OFF
OFF
OFF
2.040 (51.82)
.67 (17 .02)
4 Pole
Panel Mounting Cutout
1 Pole
.770 (19.6) 1.525 (38.7)
2 Pole
2.280 (57 .9)
3 Pole
3.040 (77 .2)
3.000 (76.20)
ON
ON
ON
ON
2.187 (55.55)
OFF Notes: Mounting Detail Tol.: .005 (.13) unless noted Panel Thickness: .047 (1.2) to .110 (2.8)
OFF
OFF
OFF
Outline Dimensions
W9 Series
Series Trip Model
.281 (7 .14) 1.845 (46.86) .313 (7 .95)
Series Trip Model
.750 (19.05) .375 (9.53) .375 (9.53) .750 (19.05) .750 (19.05) .750 (19.05) .398 (10.77)
LINE
ON 29
ON ON
1.940 (49.28) OFF LOAD .14 2.10 (3.56) (53.34) 2.50 (64.00)
30
OFF OFF
.218 (5.54) 2.065 (52.45)
ON ON ON ON ON ON ON ON
1.438 (36.53) 2.50 OFF OFF OFF OFF OFF OFF OFF OFF (63.5)
#10-32 STUD TERMINATION
1 POLE TAPPED #6-32 X .16 (4.06) DEEP M3 X 0.5 OPTIONAL
.74 (18.8)
2 POLE 1.500 (38.10) 2.250 3POLE (57 .15) 3.000 (76.20)
4 POLE
Series Trip Model With Common Enclosed Auxiliary Switch
Panel Mounting Cutout Detail
.750 (19.05) .732 (18.59) .750 (19.05) Notes: 1. Terminal protrusion dimensions are referenced from the back of the mounting panel. 2. Mounting detail tolerance .005 (13) unless noted. 3. Outline drawing tolerance .015 (.38) unless noted. Dimensions in brackets ( ) are in millimeters.
www..com
.281 (7 .14) LINE C NO NC LOAD
2.46 (62.48) 'A' STYLE
.750 (19.05)
.385 (9.78) .907 (23.04)
1.450 (36.83)
1.940 (49.28)
2.065 (52.45)
2.50 (64.00)
2X O .156 (3.96) PER POLE 3.04 (77 .2)
2.28 (57 .9)
.76 (19.3) 1.52 (38.6)
1 POLE 2 POLE 3 POLE 4 POLE
Tyco Electronics 700 Westpark Drive Peachtree City, GA 30269-1498 Specifications and availability subject to change without notice. 13C9699 Printed in U.S.A. IH/2-00


▲Up To Search▲   

 
Price & Availability of W68-XXXXX

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X